About this product
Jenis GaransiGaransi Internasional
BrandSchneider Electric
Product description
Yellow Station - 1 Red Mushroom Head Push Button ø40 Turn To Release 1NC
Barang Original Schneider 100% dan Bergaransi Resmi 12 Bulan
This Harmony XALK yellow (RAL1021) control station is ideal for a clearly visible emergency shutdown of any machine. This yellow control station enables machine builders to easily add control and signalling functionality on their machines, with permanent modifications or damage to their machine body. It is designed for simple and mass production machines, textiles, packaging, handling small lifting systems, control of garage doors, rolling shutters, smoke extraction vents. It offers emergency stop and emergency switching off functions. It is impact resistant, dust resistant, water resistant, corrosion resistant, and vibration resistant thanks to its IP69 / IP67 / IP66 / IP69K, making it ideal for operation in harsh environments.
1. Range of product : Harmony XALK
2. Product or component type : Complete control station
3. Device short name : XALK
4. Product destination : For XB5 Ø 22 mm control and signalling units
5. Control station application :
- Emergency switching off function
- Emergency stop function
6. Colour of base of enclosure : Light grey (RAL 7035)
7. Colour of cover : Yellow (RAL 1021)
8. Material : Polycarbonate
9. Operator profile : 1 mushroom head push-button
10. Operators description : Red unmarked 1 NC
11. Reset : Turn to release
12. Control station composition : 1 mushroom head Ø 40 mm push-button, red 1 NC unmarked marking
13. Contact operation : Slow-break
- 1 knock-out for cable entry 0…14 mm
- 2 knock-outs for Pg 13 cable gland and ISO M20 0…12 mm
2. Product weight : 0.194 kg
3. Resistance to high pressure washer : 7000000 Pa at 55 °C, distance : 0.1 m
4. Positive opening : With conforming to IEC 60947-5-1 appendix K
- 1.5 mm (NC changing electrical state)
- 2.6 mm (NO changing electrical state)
6. Operating force : 44 N NC + NO changing electrical state
7. Mechanical durability : 300000 cycles
8. Connections - terminals :
- Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1
- Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1
9. Tightening torque : 0.8…1.2 N.m conforming to IEC 60947-1
10. Shape of screw head :
- Cross compatible with Philips no 1 screwdriver
- Cross compatible with pozidriv No 1 screwdriver
- Slotted compatible with flat Ø 4 mm screwdriver
- Slotted compatible with flat Ø 5.5 mm screwdriver
11. Contacts material : Silver alloy (Ag/Ni)
12. Short-circuit protection : 10 A cartridge fuse type gG conforming to IEC 60947-5-1
13. [Ith] conventional free air thermal current : 10 A conforming to IEC 60947-5-1
14. [Ui] rated insulation voltage : 600 V (pollution degree 3) conforming to IEC 60947-1
15. [Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947-1
16. [Ie] rated operational current :
- 3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1
- 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1
- 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1
- 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1
- 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1
- 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
17. Electrical durability :
- 1000000 cycles, AC-15, 2 A at 230 V, operating rate
- 1000000 cycles, AC-15, 3 A at 120 V, operating rate
- 1000000 cycles, AC-15, 4 A at 24 V, operating rate
- 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate
- 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate
18. Electrical reliability :
- Λ < 10exp(-6) at 5 V, 1 mA conforming to IEC 60947-5-4
- Λ < 10exp(-8) at 17 V, 5 mA conforming to IEC 60947-5-4
1. Protective treatment : TH
2. Ambient air temperature for storage : -40…70 °C
3. Ambient air temperature for operation : -40…70 °C
4. Overvoltage category : Class II conforming to IEC 60536
5. IP degree of protection :
- IP66 conforming to IEC 60529
6. NEMA degree of protection :
7. IK degree of protection : IK03 conforming to IEC 62262
9. Vibration resistance : 5 gn (f= 12…500 Hz) conforming to IEC 60068-2-6
- 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
- 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27