Display method: 4-digit 7-segment LED
Control method: ON/OFF control, P, PI, PD, PID control
Input specification: Thermocouple: K(CA), J(IC), T(CC), R(PR), S(PR), L(IC); RTD: DPt100Ω, Cu50Ω
Sampling cycle: 100ms
Control output: Relay(250VAC~ 3A) or SSR drive(12VDC ) [ON/OFF]
Option output: Alarm 1/2
Power supply: 100-240VAC~ 50/60Hz
Display accuracy_RTD:
•At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Display accuracy_Thermocouple:
•At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit
•Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit
Hysteresis(adjustable sensitivity): 1 to 100℃/℉(0.1 to 50.0℃/℉) variable
Proportional band: 0.1 to 999.9℃/℉
Integral time: 0 to 9999 sec
Derivative time: 0 to 9999 sec
Control period: 0.5 to 120.0 sec
Manual reset: 0.0 to 100.0%
Environment_Ambient temperature: -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity: 35 to 85% RH, storage: 35 to 85% RH